Dual Refrigeration Cabinet
The Dual Refrigeration Cabinet is a high-performance enclosure designed for environments with strict temperature control requirements, such as data centers, telecom rooms, and industrial automation facilities. Equipped with both a primary and backup cooling system, it ensures uninterrupted operation even in the event of a cooling unit failure. Its intelligent auto-switching mechanism, temperature monitoring, and high-efficiency heat dissipation make it ideal for mission-critical applications. Built with energy-saving and environmental adaptability in mind, this cabinet offers reliable protection for sensitive electronic equipment, significantly reducing the risk of overheating and downtime.
40U Product Specifications:(Support Customization)
| Cabinet Section: | |
| Model Number | K-ODC99200C03 |
| Dimensions | W900mm×D900mm×H2000mm |
| Internal Structure | 19 inch 40U rack space |
| Material | Galvanized steel(304 or 316 stainless steel, or 5052 aluminum) |
| Thermal Insulation | 20mm PEF insulation |
| Door | A front door with a three point mechanical lock |
| Cable Entry | Bottom cable entry/exit |
| Protection Grade | IP65 |
| Surface Treatment | Powder coating |
| Color | RAL7035 |
| Load Capacity | ≥ 1000kg |
| Installation Type | Floor-mounted with anchor holes |
| Operating Temperature | -40℃ ~ +65℃ |
Functional Configuration: |
|
| Power Distribution Unit | AC Input: 1×63A/2P,1×63A/2P Automatic dual power transfer switch,SPD 1×40KA/2P AC Output: 25A/1P×2, 16A/1P×3, 6A/1P×2 |
| Environmental Monitoring Unit | Real-time monitoring of utility power, battery, and power distribution systems Air conditioner status monitoring and fault alarms Supports environmental sensors: temperature, humidity, door, water leakage, smoke Remote control of switches and access door management Communication via RS485/RS232, TCP, SNMP protocols Supports SMS alerts, audible-visual alarms, log recording, and remote management |
| UPS | Input Input Frequency: 50Hz / 60Hz (Auto-sensing) Phase: Single Phase Output Output Capacity: 6KVA(4800W) Output Voltage: 220VAC ±1% Output Frequency: 50Hz / 60Hz ±0.1Hz Transfer Time: 0ms (Online) Bypass Output: Supports manual and automatic bypass External Battery Battery Type: Sealed Lead-acid or Lithium battery Battery Voltage: 24V / 48V / 72V Typical Backup Time: Depends on battery capacity Communication & Display Display: LCD screen + LED indicators Communication Port: RS232, USB, SNMP (optional) Alarms: Battery low voltage, input fault, overload, UPS fault |
| Cooling Method | Cabinet air conditioner Cooling capacity:2 ×1500W Power input:220VAC 50Hz Communication mode:RS485 Refrigerant:R134a Protection level:IP55 |
| Lighting | 48V LED |
| Security Features | Door sensor, Smoke sensor, Water sensor, temperature sensor |
| Optional Accessories | / |